Technical Data AT4 components
Frame 38 mm
Material st/ zn
Panels double-wall 47 mm
Panel material st/ vz, powder-coated (RAL 7032)
Insulation Mineral wool
Weight per
unit area of insulation
 
55 kg/ m³
Material class of insulation A 1
Mechanical stability   Class 1 A
Housing leakage Class B
Thermal insulation Class T 3
Thermal bridge factor
 
Class TB 3
Mean sound-insulation unit
 
34 dB
Insertion attenuation De (as per DIN EN 1886)
Hz
db
125
15.8
250
24.4
500
30.2
1k
35.1
2k
35.4
4k
35.8
8k
36.5


The air-conditioner can be completely dismantled.

The air-conditioner can be used between - 30 °C and + 60 °C when installed under standard Central European climatic conditions.

If the equipment is installed at special locations (e.g. indoor pools, bathrooms, in tropical regions), the operational limits must be ascertained from the manufacturer.